R22 Capillary Tube Chart

Looking for the right capillary tube size for your refrigeration system can be a daunting task, but fear not, the R22 Capillary Tube Chart is here to help!

This chart is a lifesaver for refrigeration technicians, allowing them to choose the perfect diameter and length of capillary tube based on the system’s evaporator temperature and cooling capacity.

When it comes to sizing capillary tubes, there are a few rules to keep in mind.

  • The tube’s diameter and length both play a critical role in determining its total restriction. Interestingly, even a slight percentage change in diameter can have a more significant impact on flow than a change in length.
  • You can also change the restriction by altering the tube’s length. Longer tubes result in slower flow rates, so going to extreme lengths to increase restriction may not always be the best idea. Once the pipe length decreases, the flow rate gradually increases until it reaches a critical point where the flow rate starts to rise rapidly with each reduction in length.
  • However, when the pipe becomes too short, even small changes in length can cause significant increases in flow. At this point, the tube starts acting more like an orifice than a capillary tube.
  • As a general rule of thumb, it’s best to keep your capillary tube length between 5 and 16 feet. Of course, there are always exceptions, but staying within this range for day-to-day operations can help eliminate many problems.

When using the R22 Capillary Tube Chart, the evaporator temperature is the first parameter to consider. Take into account:

Temperature
of evaporator
Temperature
of Condenser
LBP-23,3 °C
-10°F
54,4 °C
130°F
MBP-6,7 °C
20°F
54,4 °C
130°F
HBP7,2 °C
45°F
54,4 °C
130°F

1 HP = 746W

Power electric
Compressor HP
Temperature
of Evaporator
Diameter
in
Length
m
1/4 HPHBP0,050 in3,0m
1/4 HPMBP0,036 in2,5m
1/3 HPHBP0,05in2,0m
1/3 HPMBP0,042 in3,0m
1/2 HPHBP0,050in1,5m
1/2 HPMBP0,042in2,0m
1 HPHBP0,064in1,5m
1 HPMBP0,0502,0m
1 1/4 HPHBP0,0641,5m
1 1/4 HPMBP0,0641,0m
1 1/4 HPHBP0,0641,5m
1 1/4 HPMBP0,0641,0m

Cooling Capacity

It is the cooling capacity of a compressor at a given evaporation temperature of refrigerant r22. It represents a base parameter for selection, it is measured in Btu/h, Kcal/h and some models in the international system use W, it should not be confused with electrical power, because in this case we are talking about energy in the form of heat.

Cooling
Capacity
Temperature
of Evaporator
-10 °F
Temperature
of Evaporator
25 °F
Temperature
of Evaporator
45 °F
750 Btu/h
185 Kcal/h
0.028″ – 15 ft0.028″ – 14 ft0.028″ – 13½ ft
1000 Btu/h
250 Kcal/h
0.028″ – 8 ft0.028″ – 7½ ft0.028″ – 7 ft
1250 Btu/h
312 Kcal/h
0.028″ – 5 ft0.028″ – 4½ ft ft0.028″ – 4½
1500 Btu/h
375 Kcal/h
0.031″ – 6 ft0.031″ – 5½ ft0.031″ – 5 ft
2000 Btu/h
500 Kcal/h
0.040″ – 13 ft0.040″ – 12½ ft0.040″ – 12 ft
3000 Btu/h
750 Kcal/h
0.040″ – 5½ ft0.040″ – 5 ft0.040″ – 5 ft
4000 Btu/h
1000 Kcal/h
0.052″ – 13 ft0.052″ – 12 ft0.052″ – 11½ ft
6000 Btu/h
1500 Kcal/h
0.052″ – 5½ ft0.052″ – 5 ft0.052″ – 5 ft
8000 Btu/h
2000 Kcal/h
0.064″ – 9 ft0.064″ – 8½ ft0.064″ – 8½ ft
10000 Btu/h
2500 Kcal/h
0.064″ – 5½ ft0.064″ – 5½ ft0.064″ – 5 ft
12,000 Btu/h
3000 Kcal/h
0.064″ – 4 ft0.052″ – 5 ft (2)0.052″ – 5 ft (2)
Length
Capillary
meters
0,6
mm
0,6
mm
0,7
mm
0,7
mm
0,8
mm
0,8
mm
0,9
mm
0,9
mm
-30
°C
-23,3
°C
-30
°C
-23,3
°C
-30
°C
-23,3
°C
-30
°C
-23,3
°C
100 Kcal/h
400 Btu/h
2,63
m
2,76
m
      
120 Kcal/h
480 Btu/h
1,811,90      
130 Kcal/h
520 Btu/h
1,541,62      
140 Kcal/h
560 Btu/h
1,331,393,063,20    
150 Kcal/h
600 Btu/h
1,151,212,662,79    
160 Kcal/h
640 Btu/h
1,011,062,332,45    
170 Kcal/h
680 Btu/h
  2,072,17    
180 Kcal/h
720 Btu/h
  1,841,93    
190 Kcal/h
760 Btu/h
  1,651,733,423,58  
200 Kcal/h
800 Btu/h
  1,491,563,083,23  
215 Kcal/h
860 Btu/h
  1,291,352,652,78  
230 Kcal/h
920 Btu/h
  1,121,182,312,42  
245 Kcal/h
980 Btu/h
  0,991,042,032,13  
260 Kcal/h
1040 Btu/h
    1,801,893,423,59
275 Kcal/h
1100 Btu/h
    1,601,683,053,20
300 Kcal/h
1200 Btu/h
    1,341,412,552,68
320 Kcal/h
1280 Btu/h
    1,171,232,232,35
340 Kcal/h
1360 Btu/h
    1,041,091,972,07
360 Kcal/h
1440 Btu/h
      1,751,84
380 Kcal/h
1520 Btu/h
      1,571,65
400 Kcal/h
1600 Btu/h
      1,411,48
450 Kcal/h
1800 Btu/h
      1,111,17
Length
Capillary
meters
1
mm
1
mm
1,2
mm
1.2
mm
1,5
mm
1.5
mm
-30
°C
-23,3
°C
-30
°C
-23,3
°C
-30
°C
-23,3
°C
340 Kcal/h
1360 Btu/h
3,53
m
3,70
m
    
360 Kcal/h
1440 Btu/h
3,133,29    
380 Kcal/h
1520 Btu/h
2,802,94    
400 Kcal/h
1600 Btu/h
2,522,64    
450 Kcal/h
1800 Btu/h
1,972,07    
500 Kcal/h
2000 Btu/h
1,581,66    
550 Kcal/h
2200 Btu/h
1,301,363,563,74  
600 Kcal/h
2400 Btu/h
1,081,142,963,11  
650 Kcal/h
2600 Btu/h
0,920,962,502,63  
700 Kcal/h
2800 Btu/h
  2,142,25  
750 Kcal/h
3000 Btu/h
  1,851,95  
800 Kcal/h
3200 Btu/h
  1,621,70  
850 Kcal/h
3400 Btu/h
  1,421,50  
900 Kcal/h
3600 Btu/h
  1,261,33  
950 Kcal/h
3800 Btu/h
  1,131,18  
1000 Kcal/h
4000 Btu/h
  1,011,063,583,68
1100 Kcal/h
4400 Btu/h
    2,973,01
1200 Kcal/h
4800 Btu/h
    2,512,50
1300 Kcal/h
5200 Btu/h
    2,142,11
1400 Kcal/h
5600 Btu/h
    1,851,80
1500 Kcal/h
6000 btu/h
    1,621,56
1600 Kcal/h
6400 Btu/h
    1,431,36

Length
Capillary
meters
0,7
mm
0.7
mm
0,8
mm
0.8
mm
0,9
mm
0.9
mm
1
mm
1
mm
kcal/h5
°C
7,2
°C
5
°C
7,2
°C
5
°C
7,2
°C
5
°C
7,2
°C
100        
1204,544,68      
1303,904,02      
1403,363,47      
1502,923,03      
1602,592,68      
1702,292,374,674,82    
1802,042,114,164,30    
1901,831,893,733,88    
2001,661,723,403,52    
2151,431,492,943,04    
2301,251,302,562,654,794,95  
2451,091,142,262,354,264,41  
260 1,012,012,093,793,92  
275  1,801,873,383,50  
300  1,501,562,832,945,00 
320  1,311,372,502,604,404,55
340  1,161,222,212,303,894,02
360  1,041,091,972,053,463,58
380    1,761,833,123,24
400    1,581,652,822,93
450    1,251,312,222,31
500     1,051,781,86
550      1,471,54
600      1,231,29
650      1,031,09
Length
Capillary
meters
1,2 nn1.2 nn1,5 nn1.5 mm
kcal/h5
°C
7,2
°C
5
°C
7,2
°C
5004,76 m4,93 m  
5503,964,11  
6003,323,45  
6502,822,93  
7002,412,52  
7502,092,18  
8001,841,93  
8501,631,71  
9001,441,524,87 
9501,281,354,364,53
10001,151,213,924,07
1100  3,213,35
1200  2,712,84
1300  2,302,41
1400  1,962,06
1500  1,691,78
1600  1,461,55

Chiller Fault Finding

Chiller Fault Finding is divided into:

  1. Chiller failures in the refrigeration cycle.
  2. Chiller failures in the control system.
  3. Chiller failures originating in the hydraulic circuit.

Chiller failures in the refrigeration cycle include:

  • Low suction pressure in a chiller:
    • Caused by a lower amount of refrigerant in the circuit due to leaks or improper recharge.
    • Insufficient water flow through the cooler or evaporator compared to the chiller’s capacity.
    • Reduced thermal load in the application.
    • Inadequate chiller control strategy with an excessive number of compressors operating.
    • Issues with the expansion valve or temperature sensors.
    • Lack of maintenance and poor cleaning of the evaporator.
    • Chiller not adequately adapted to partial loads due to low IPLV values.
  • Compressor with a flooded start:
    • Occurs when refrigerant migrates into the compressor crankcase while it is off.
    • Migration is caused by temperature, concentration, and pressure differences.
    • The presence of liquid refrigerant in the crankcase displaces and dilutes the compressor oil, leading to wear in vital parts.
    • Proper operation of the heating elements in the compressor crankcase and adherence to manufacturer’s design and control strategies are crucial to prevent this failure.
  • Refrigerant liquid in the suction of the compressor in operation:
    • Refrigerant should only enter the suction of the chiller compressor in a vapor state.
    • Liquid refrigerant cannot be compressed by the compressor and can cause severe damage.
    • Improper control strategies or issues with the expansion valve can result in liquid refrigerant in the compressor suction.
    • Modern chillers may experience inadequate control strategies due to sensor problems.
    • Proper functioning of the expansion valve is essential to eliminate this problem.
  • High discharge temperature:
    • High discharge temperatures degrade the compressor oil and affect vital properties such as viscosity.
    • Potential causes should be investigated and addressed.
  • Lubrication-related failures:
    • Check oil traps, the compressor station’s lubrication system, oil separator, and details in new installations such as pipe diameter.

What failure presents the compressor according to the color of the oil?

  • Colorless or light yellow:
    • Indicates good performance.
  • Black oil:
    • Indicates carbonization caused by air in the system or the presence of wear particles containing iron.
    • Change compressor oil and oil filter.
  • Light brown oil:
    • Use an acid test kit to test for acidity in a sample of the compressor oil.
    • Change the compressor oil if the test indicates acidity.
    • Indicates that dissimilar metal surfaces have become coated with copper due to moisture in the system.
  • Brown oil:
    • Indicates air in the system or high compressor temperature.
    • Chemicals can cause oxidation, resulting in the oil turning brown.
    • Change compressor oil if the test indicates acidity.
    • Copper plating may occur due to moisture combining with the refrigerant, forming an acidic solution that dissolves copper-containing materials.
    • Inspect and replace worn or damaged components.
  • Metallic gray oil:
    • Indicates the presence of wear and particles containing aluminum.
    • Usually caused by bearing wear or piston scoring.
    • Disassemble the compressor and inspect for worn or damaged components.
    • Change the oil and oil filter.
  • Green oil:
    • Green compressor oil indicates water in the system, and copper coating may have occurred.
    • Disassemble the compressor and shaft seal.
    • Inspect wheels, gears, and rotors.
    • Replace the oil separator, oil, and oil filter.

What are the breakdowns of a chiller evaporator?

The problems in the evaporator of a chiller are presented by:

  • A dirty evaporator with scale buildup that hinders heat exchange between the refrigerant in the refrigeration circuit and the chilled water.
  • A low flow of water to be cooled can cause the evaporator to freeze.
  • A low refrigerant charge in the chiller’s refrigeration cycle can result in poor cooling quality.
  • Inadequate chiller control strategies can lead to excess or insufficient cooling in the chiller evaporator.
  • Failure of water or chiller refrigerant temperature sensors can result in inadequate control strategies.

Chiller condenser high-pressure faults:

Depending on the cooling method of the condenser, the following issues may arise:

  • For air-cooled condensers, verify the adequate fan speed.
  • Check the condition and cleanliness of the condenser for efficient thermal exchange.
  • If the condenser is water-cooled, check for the concentration of embedded particles on the condenser walls that may impede heat exchange.
  • Insufficient cooling tower performance can hinder proper freshwater conditioning.

Chiller failures in the control system:

Chiller sensor failures:

  • Temperature sensor failures:
    • Temperature sensors in chillers are often of the thermoresistance type.
    • Resistance thermometers, such as the PT1000, provide linear temperature signals.
    • Use an acid test kit to check the acidity of the compressor oil sample.
    • Change the compressor oil if the test indicates acidity.
    • Failure of temperature sensors can cause the unit to stop to prevent damage due to insufficient water flow.
    • The compressor discharge temperature sensor informs the controller of the superheated steam temperature at the compressor outlet.
    • Monitor values provided by the temperature sensor to prevent damage to the oil or compressor components.
  • Pressure sensor failures:
    • The discharge pressure sensor allows control measures to be taken to prevent chiller problems.
    • The suction pressure sensor recognizes refrigerant overheating at the chiller evaporator outlet.
    • Use a digital multimeter to measure the supply voltage and signal and a pressure gauge to measure exact pressures.
    • Compare the pressure values from the gauge with those transformed by the sensor.
    • If the pressure sensors send out-of-range signals to the controller, the equipment will be stopped.

Ensure proper functioning of sensors and address any faults in the thermistor, engine cooling system solenoid, or wiring.

Hydraulic circuit failures:

Air inside pipes: Air can be introduced into the pipes, affecting heat exchange. The percentage of air dissolved in the water depends on the temperature and pressure. Higher pressure leads to a higher content of dissolved air in the water. With higher temperatures, the dissolved air content decreases. Under conditions of high temperature and low pressure, oxygen is released in greater proportion. Changes in pipe slope cause pressure variations that can release dissolved air, forming air pockets. The air pockets move through the pipeline and accumulate in higher areas. Air pockets also accumulate in exchangers, affecting their performance.

Issues with the expansion vessel: The expansion vessel has a gas-filled membrane that can absorb changes in water volume without affecting the system. To avoid failures, it is necessary to know the manometric height and the minimum and maximum working pressures when calculating an expansion vessel. Having very large or small vessels does not achieve the desired function. The operation of the vessel at different locations (highest point, basement, before or after pumping equipment) differs. A pressure measuring device should be installed in the supply line to the vessel as a standard requirement. The expansion vessel marks the reference pressure value of the closed circuit. Pressure measuring equipment must be installed in the supply line to the vessel.

Failures with pumps in installations with chillers: Installations with chillers require centrifugal pumps to move water through the pipes.

PRIMARY PUMPS: Responsible for sending water to the chiller.

SECONDARY PUMPS: Responsible for sending chilled water to the desired point.

CONDENSER PUMPS: In the case of chillers with a water-cooled condenser, an additional pump system is required to deliver water to the condenser and cooling tower.

Possible pump failures and solutions:

  • Pump on but no water supply:
    • Verify that the suction pipe is full and free of air or obstructions.
    • Check the condition of the foot valve and filter for any blockages.
    • If there is no water in the suction pipe, prime the pump by removing the priming plug and adding water until no air comes out and the water overflows. If the pipe doesn’t fill, replace the foot valve.
    • Check the motor’s rotation direction.
  • Low water flow:
    • Air ingress in the suction pipe or through the seal.
    • If the pump has gaskets, replace them if excessive fluid leakage is observed.
  • Motor overload:
    • Check if the equipment is operating within the correct range.
    • Throttle the discharge valve to decrease pump flow.
    • Inspect impeller blades for damage that may cause imbalance and vibrations affecting motor operation.
    • Check motor bearings, pump shaft, and insulation in motor coils.
    • Ensure proper alignment.
    • Loss of prime in the pump.
    • Defective foot valve and water leakage.
    • Water leaks due to damaged seals or gaskets.
    • Leaks in piping or fittings.
    • Air ingress in the suction pipe or excessive leakage in the discharge area.
    • Premature failure of seals or gaskets.
    • Unbalance or misalignment.
    • Lack of lubrication.
    • Verify that the pump is not running idle.

Chiller Refrigerant Subcooling

Chiller Refrigerant Subcooling is a critical parameter in engineering that measures the temperature difference between the liquid refrigerant at the chiller condenser outlet and the gas condensation temperature. This differential can be calculated using the following formula:

Subcooling = Refrigerant outlet temperature – Condensing temperature.

Conversely, the outlet temperature can be determined by subtracting the subcooling value from the condensing temperature:

Outlet temperature = Condensing temperature – Subcooling.

Let’s delve into the calculation of air-cooled refrigerant subcooling for a comprehensive understanding. Consider a chiller operating under ideal conditions with a subcooling value of 3°C in an ambient environment of 30°C. Typically, the condensing temperature of a refrigerant ranges from 10°C to 20°C above the ambient temperature. For this example, we will assume an average condensing temperature of 15°C.

Given an ambient temperature of 30°C, the condensing temperature can be calculated as follows:

Condensing temperature = Ambient temperature + 15°C Condensing temperature = 35°C + 15°C = 50°C.

To determine the refrigerant’s outlet temperature at the chiller condenser, we use the following formula:

Outlet temperature = Condensing temperature + Subcooling Outlet temperature = 50°C – 3°C = 47°C.

Refrigerant subcooling plays a vital role in chiller systems, as it significantly impacts their performance and energy efficiency. Greater subcooling indicates that the refrigerant remains further away from the vapor phase as it reaches the condenser outlet. This enhanced subcooling directly correlates with better condenser operation, potentially leading to lower chiller high pressures and reduced electrical energy consumption.

Moreover, subcooling affects the percentage of refrigerant that evaporates in the expansion valve, where a sudden pressure drop occurs. It is important to note that higher subcooling levels result in a reduced amount of refrigerant evaporating as flash steam during this process. By minimizing evaporation in the expansion valve, system efficiency improves, as the liquid refrigerant is primarily responsible for heat absorption in the chiller’s evaporator. Lower refrigerant evaporation also results in reduced overheating, further enhancing the chiller’s overall energy efficiency.

To optimize Chiller Refrigerant Subcooling, it is crucial to follow these best practices:

  1. Regularly clean air-cooled condenser coils to maintain optimal performance.
  2. Ensure proper airflow from the condenser cooling fans by conducting regular checks.
  3. Implement suitable maintenance procedures for the cooling tower water circuit in air-cooled condensers to prevent fouling and contamination, which can hinder condenser heat exchange and cooling efficiency.
  4. Maintain the correct airflow rate and ensure the cooling tower is in good condition for air-cooled condensers.

By adhering to these practices, you can enhance Chiller Refrigerant Subcooling, leading to improved chiller performance, energy efficiency, and ultimately, a more sustainable operation.

Optimizing Refrigeration Performance with Mollier Diagram: Subcooling Insights

The Mollier diagram is crucial in refrigeration engineering, providing valuable insights into subcooling processes for optimizing system performance. Engineers can precisely determine the ideal subcooling requirements, ensuring efficient heat transfer and preventing undesired vaporization. By leveraging the Mollier diagram, subcooling levels can be fine-tuned for specific operating conditions, enhancing overall efficiency and minimizing risks. Explore our comprehensive video explanation for a deeper understanding of the Mollier diagram’s practical applications in refrigeration systems.

Chiller Refrigerant Superheat

Chiller Refrigerant Superheat: A Guide to Understanding and Calculating

When it comes to chiller operation, there’s one important factor you don’t want to overlook: superheat. But what exactly is superheat? Put simply, it’s the difference between the evaporation temperature of the refrigerant gas in the chiller evaporator and the temperature at the compressor inlet.

https://youtu.be/wGfbexzhn38

To calculate superheat, you can use this equation:

Superheat = Evaporator outlet temperature – Compressor inlet temperature

Let’s take a closer look at two different types of chiller evaporators and how to calculate their superheat.

Dry Chiller Evaporator:

If you’re using a chiller with a thermostatic expansion valve for air conditioning, you’ll want to know the evaporation temperature, which is typically around 7°C. The temperature at the evaporator outlet (compressor inlet) will depend on the cooling load and valve setting, but let’s say it’s around 11°C.

Using the superheat equation, we can calculate:

Superheat = Evaporator outlet temperature – Compressor inlet temperature Superheat = 11°C – 7°C = 4°C

Chiller Flooded Evaporator:

In this type of evaporator, the liquid refrigerant from the refrigeration circuit is fed through a float valve to maintain a constant level inside the casing. As the cooling load varies, a refrigerant level control valve ensures that the liquid level is maintained in the shell. The outlet of the refrigerant from the evaporator is located at the top, and is always above the level, so the refrigerant must be in a vapor state to rise and reach the outlet point.

Since the refrigerant leaving the flooded evaporator is a newly formed vapor, the outlet temperature is the same as the evaporation temperature, which we know is around 7°C. Using the superheat equation, we can calculate:

Superheat = Evaporator outlet temperature – Compressor inlet temperature Superheat = 7°C – 7°C = 0°C

Why does superheat matter?

For one, it allows the expansion valve to regulate the amount of refrigerant that enters the chiller’s evaporator. If superheating is greater than zero in dry evaporators, it indicates that all the refrigerant is in the vapor state before entering the compressor. Excessive overheating can cause very high temperatures at the compressor outlet, which can affect the oil.

To improve the efficiency of modern large chillers and refrigeration equipment, superheat should be as close to zero as possible, always above. In chillers with bulb thermostatic expansion valves, the standard superheat value is usually 5°C maximum.

By understanding and calculating chiller refrigerant superheat, you can keep your system running smoothly and efficiently.

Water treatment for chiller system

Water treatment for the chiller system generally includes the following filtration steps.

  • Filtration and Ultrafiltration Processes.
  • Ion exchange and water softening.
  • Addition of chemicals.
  • Reverse osmosis systems.

Water Treatments for Chillers

The precise treatment processes fluctuate depending on the cooling tower’s needs, the state of the circulation, and the feed water. Next, we will explain the basic steps mentioned above.

Filtration and Ultrafiltration:

  • Filtration is a process required to remove impure substances, such as organic matter and suspended solids, from the feed water.
  • It is more effective to use filtration systems at the initial stage, as the eradication of suspended particles upstream can maintain the safety and efficiency of membranes and ion exchange resins against fouling

Ion exchange for water softening:

  • If the water contains large amounts of hardness, there are certain treatments available to remove it.
  • Water softening systems are effective at removing ions that cause water to increase in hardness.
  • Typically, these ions tend to be magnesium, calcium, and iron ions which are selected and removed.
  • Ion exchange resins provide a similar function by replacing these hardening ions with non-hardening ions, such as sodium ions.

Addition of chemicals:

  • At this stage, chemicals such as anti-acid bicarbonates and other inhibitors are usually added to prevent the build-up of scale deposits.
  • Fortunately, pretreatment can decrease the number of chemicals required during this stage, which is preferable since many of these chemicals are expensive.

Reverse Osmosis Systems:

  • Reverse osmosis systems remove virtually all unwanted dissolved solids by filtering the feed water using high-quality semi-permeable membranes.
  • The reverse osmosis process is incredibly efficient at producing ultrapure water for consumption or use in a variety of applications and is often the backbone of any well-designed water purification system.

Why is it essential to treat chiller water?

  • While many problem areas can affect chiller performance, perhaps the biggest culprit is the contamination of its heat transfer surfaces.
  • If a chiller’s tubes become covered or clogged with scale, sediment, or biological growth, their ability to transfer heat is significantly reduced.
  • The rate at which this fouling occurs is highly dependent on the quality of the water in the system, but even a thin layer of contamination can significantly reduce overall efficiency.
  • Chemical water treatment helps prevent this buildup of contaminants on heat transfer surfaces.
  • Open systems, such as condenser water systems, that include a cooling tower require an ongoing chemical water treatment program.
  • Closed systems generally require only a one-time chemical treatment.
  • Concentration levels of water treatment chemicals that are too low, or that do not match the conditions encountered, will be ineffective.
  • The wrong chemicals or concentrations that are too high can damage internal components.
  • Even with a good water treatment program, the cleaning of chiller condenser tubes will be necessary.
  • With a brush, annual cleaning can remove mud buildup, biological growth, and any loose material.
  • If there is a buildup of scale on the tubes, it will usually need to be removed by a chemical cleaning process.

Glycol chiller maintenance

Glycol chiller maintenanceis of special importance to maintain the quantity and quality of the chilled water that is supplied and to avoid inconveniences with freezing of the fluid, deterioration of facilities, and heat exchange problems.

Ethylene glycol:

Ethylene glycol is an efficient and generally less expensive antifreeze protectant than propylene, but it is toxic and therefore facilities must adhere to proper safety protocols when applying or discharging it.

Propylene glycol

This is a non-toxic alternative to ethylene glycol, but it is also more expensive. For facilities that process food or those with green or organic initiatives, this is the obvious choice.

Aspects of Glycol Maintenance in Chillers:

  • Checking for good glycol pressure is one way to verify that the pump is working and that the chiller is delivering the normal amount of glycol.
  • An extreme drop in pressure could mean there is a problem with your process piping or a low glycol level in your reservoir.
  • Checking the glycol level in your reservoir is easy to do as there is an external sight tube.
  • Low glycol levels can cause major difficulties throughout the cooler.
  • Checking the glycol mix is ​​done with a refractometer.
  • Keeping the glycol at a 26.5 Brix mix is ​​a must in your cooler. That results in 35% propylene glycol to 65% water.
  • Test the freezing point of the mixture.
  • Adjust or replace mix as needed. Typically, the range is 20-25% glycol; however, each manufacturer is different, so check their recommendations before making any changes.
  • If the glycol levels are too low, or the glycol in your system breaks down, you may be in for some expensive difficulties.
  • Calculate the lowest temperature your system can be subjected to, to determine the desired freezing point. Then refer to the freezing point table (for example, the one above) to find the desired concentration.
  • Ideally, the pH should be between 8 and 10. If your pH is too low, you may need to add additional inhibitors or flush and refill the system, depending on your lab results.
  • Measurement of the alkalinity reserve will help determine whether the liquid can be restored. If the reserve alkalinity is depleted, the useful life of the fluid has expired and the system will need to be flushed and refilled.
  • Automotive antifreeze should never be used because it is formulated to cool the engine and can cause difficulties with flow rates with pressures, and reduced heat transfer.
  • Uninhibited glycol and water mixtures are highly corrosive. Inhibitors protect against corrosion, scale, and rust and act as pH buffers and biocides.
  • Never use less than 25% glycol, this will ensure that an adequate amount of inhibitors is present. Never over mix – use only the concentration of glycol needed to protect equipment.
  • DO NOT mix different types of glycol or different brands. Incompatibilities can lead to formulation separation, plugging filters, strainers, and pump suctions, as well as reducing its transfer properties.
  • Check local regulations for measures regarding glycol and antifreeze solutions. Soil structure, water table, drainage, and disposal may be things to consider.
  • A glycol solution is denser than water and does not offer the same level of heat transfer as water. Therefore, it will produce slightly reduced cooling capacity, exclude pumping power consumption, and highlight fluid temperature differences.
  • Most systems use running water from the “tap”. However, the proper application of inhibitors is vitally important to prevent damage to the cooling system.
  • Using distilled, demineralized, deionized, or RO water will eliminate all the unpredictability associated with public mains water.
  • The chilled water system must be flushed, cleaned, and sanitized before adding a new water-glycol solution.
  • The water and glycol solution should be sampled and analyzed periodically to ensure that no problem arises.

Chiller R-123

The Chiller with R-123 is mainly a low-pressure centrifugal chiller with a water-cooled condenser, used for industrial air conditioning and climate control of large buildings.

What should you know about R-123 in chillers?

  • Along with another hydrochlorofluorocarbon (HCFC) refrigerants, R-123 is being phased out through control measures specified in the Montreal Protocol.
  • For example, in the United States, R-123 should have been discontinued in new equipment as of January 1, 2020.
  • The recycled R-123 is expected to be available for service in the foreseeable future (EPA 2014).
  • R123 was introduced in the early 1990s as an alternative to R11 in centrifugal chiller applications.
  • Although r-123 is enormously effective and popular in large refrigerators around the world, it was largely rejected in Europe due to its B1 toxicity, after prolonged inhalation was found to cause an increased incidence of benign tumors in the rat liver, pancreas, and testes.
  • In keeping with the R-123 phase-out dates, alternative low-pressure refrigerant candidates have been used, proposed, evaluated, and in some cases, qualified for use in new and existing equipment designs. Two of these are alternates, R-514A and R-1233zd (E).
  • A possible direct replacement for R123 in existing chillers is the Chemours blend, originally known as DR-10 and now Opteon XP30. called R-514A.
  • The R-514A refrigerant mixes HFO 1336mzz (Z) (74.7%) with trans-1,2-dichloroethene (25.3%), a gas not previously used in refrigerants.

Where to learn all about chillers?

We have prepared a complete training in chilled water installations with chillers.

Chiller Training Courses

Chiller R-22

Many facilities have R-22 Chillers that have years of reliable, efficient service ahead of them.

But when operating with this refrigerant, they are equipment that is subject to international disposal due to depleting the ozone layer. Many are now looking to upgrade their equipment with an alternative refrigerant that is readily available, cost-effective, and environmentally preferred throughout the life of the chiller.

What are the options for Chillers with R-22 that are still in use?

  • Certainly, it is always desirable to replace an old R-22 cooler with a newer, more efficient cooler, but it is not always practical from a budget point of view.
  • For small tonnage chillers loaded with R-22, the most likely alternative for a retrofit is the HFC refrigerant, R-407C.
  • Although there is a moderate penalty of 5 to 10 percent for capacity and efficiency, R-407C has been available for many years for low-capacity chillers.
  • It is worth noting that R-407C is a mixed refrigerant, but for small tonnage chillers with DX-style evaporators, this will not affect performance, and no significant equipment modifications would be necessary.
  • While alternative refrigerants can generally be used to upgrade older generation refrigerants with similar pressures, the upgrade comes at the expense of reduced capacity and efficiency.
  • If for example you have a 100 TRF chiller and the particular application requires all those 100 TRF to maintain the design temperature, then a reduction in capacity would not be acceptable. The thermodynamic properties will determine what the refrigerant mass flow rate will be in a given application.
  • The capacity of the thermostatic expansion valve is based on the physical dimensions of the valve pin and port, the system conditions, and the thermodynamic properties of the refrigerant. If the mass flow requirement of the replacement refrigerant is significantly higher than the mass flow requirement for R-22, then the existing R-22 TEV would have insufficient capacity for the replacement refrigerant.
  • With R-407A and R-407C with mass flow rates similar to R-22, the original selection of R-22 TEV is well suited for application with both refrigerants.
  • Other refrigerants have a higher mass flow requirement than R-22, resulting in the original R-22 TEV being smaller for each.
  • The most notable capacity deficiency is with R-434A. Additionally, the manufacturer of R-434A states that its refrigerant requires a TEV element that is compatible with R-502 (R-404A).
  • R-404A shows good capacity compared to R-22. However, with a 42% higher mass flow requirement, a TEV replacement will be required. Plus, it has a nine percent reduction in efficiency.
  • R-417A is shown to have a good mass flow requirement compared to R-22, which means that a TEV replacement will not be required. But a 14% loss of capacity probably wouldn’t be the best option.
  • R-407C shows a slight increase in capacity compared to R-22, a very close mass flow requirement compared to R-22, and a lower drop efficiency of three percent. What’s more.
  • The R-407C has been off-patent for several years. It is widely distributed and reasonably priced. As such, the industry has viewed R-407C as the most common replacement for R-22 in comfort cooling applications.
  • Systems that do not work properly with R-22 will not work properly after refrigerant conversion. Elastomer seals tend to leak after conversion because R-22 has the most aggressive swelling influence on elastomer seals, so after conversion, the seal will effectively shrink.
  • To avoid any potential leakage after conversion, it is recommended to replace all elastomer seals.
  • All TEV in the system should be checked for the proper superheat setting and adjusted as necessary.
  • It must be remembered that the temperature at the outlet of the valve will be lower than the evaporation temperature of the last particles of liquid that are boiling, this is due to sliding For existing R-22 screw and centrifugal chillers, R-134a is often the best upgrade option.
  • While this will lead to a reduction in capacity, which can go up to 35 percent, modifications often result in a more efficient package.

Where to learn all about chillers?

We have prepared a complete training in chilled water installations with chillers.

Chiller Training Courses

Multistack Chiller

The capacity of the Modular Air Cooled Multistack Chillers ranges from 10 to 840 tons of refrigeration.

ASP010X Multistack Cooler:

It is a chiller with two scroll compressors in tandem of 5 tons refrigeration each, which works with R-410A refrigerant.

ASP015X Multistack Cooler:

It is a chiller with two scroll compressors in tandem of 7.5 tons refrigeration each, which works with R-410A refrigerant.

ASP020X Multistack Cooler:

It is a chiller with two scroll compressors in tandem of 10 tons refrigeration each, which works with R-410A refrigerant.

ASP030X Multistack Cooler:

It is a chiller with two scroll compressors in tandem of 15 tons refrigeration each, which works with R-410A refrigerant.

ASP060X Multistack Cooler:

It is a chiller with two scroll compressors in tandem of 30 tons refrigeration each, which works with R-410A refrigerant.

Chiller Multistack MSS:

This series of chillers are available in 105, 135, 145, and 165 tons refrigeration. The module design incorporates two refrigerant circuits, each with a tandem scroll, working with R-410A. Modules can be combined to achieve capacities of up to 1,320 tons of cooling capacity.

Chiller Multistack VME II:

  • They are Modules that work with scroll compressors of 105, 135, 145, and 165 tons of capacity, to create chillers of up to 1,320 tons of capacity.
  • True-VariableTM Speed ​​Displacements Available for Modules from 10 to 50 Ton, Integrated Modulator Valves provide precise control of head temperature and pressure.

MAGLEV MS Series Multistack Centrifugal Cooler:

MS models 0122F, 0132F, 0152F, 0162F, 0192F, 0202F, 0242F, 0292F, 0332F, 0392F, 0402F, 0412F, 0482F, 0542F, 0602F, 0622F, 0702F, 0802F, 1002F, 5122F, 5202F, 1202F 519 519, 5202F, 1202F

This series works with a water-cooled condenser, with an oil-free centrifugal compressor, manufactured by Danfoss Turbocor. that uses magnetic bearings. Two-stage centrifugal compression, variable speed permanent magnet motor, and intelligent electronic controls result in the highest efficiency, works with R134a.

Where to learn all about chillers?

We have prepared a complete training in chilled water installations with chillers.

Chiller Training Courses

Hitachi Chiller

Hitachi Chiller with Air Cooled Condenser:

Chiller Hitachi AZPY1 Series:

This series is made up of the RCUF45AZPY1 RCUF50AZPY1 RCUF60AZPY1 models with capacities of 160, 178, 215 KW. These chillers work with R-134a with an electronic expansion valve, with a semi-hermetic screw compressor.

Hitachi V Series Chiller:

The V series uses the DC inverter type scroll compressor, which encompasses 25% to 100% capacity control, allowing precise matching of building loads, and reducing energy input. unit, uses R410a refrigerant

Water Cooled Hitachi Chiller:

Chiller Hitachi WZPY Series

This series is made up of the RCUF50WZPY RCUF65WZPY RCUF80WZPY models, with a capacity of 190, 238, 298 KW, which works with a screw compressor with R-134a refrigerant.

Chiller Hitachi Direct-drive with VSD:

This series of chillers is designed for capacities between 300 and 1100 tons of refrigeration, with a centrifugal compressor. It is identified with the acronym HC-F_D_GFVG HC-F_D_GXVG with two-stage compressor, frequency inverter and economizer.

Chiller Hitachi Inverter GXG-SIT / GSG-SIT

This series that works with a centrifugal compressor, is made up of the HC-F300GSG-SIT models for capacities between 200 and 300 TRF, HC-F350GSG-SIT for capacities between 301 and 350 TRF, HC-F400GSG-SIT for capacities between 351 and 400 TRF.

Where to learn all about chillers?

We have prepared a complete training in chilled water installations with chillers.

Chiller Training Courses

Exit mobile version