What is the effect on the compressor when changing the refrigerant from R410A to R32 gas?

We will examine the key points regarding the replacement of R410A refrigerant with R32 gas in a previously operational air conditioning system.

Effect of Replacing R410A Refrigerant with R32 Gas in Compressor:

1. Lubrication

Both R410A and R32 utilize POE oil for lubrication. However, due to their solubility, the POE oil used with R32 tends to have lower viscosity compared to the POE oil used with R410A. Thus, replacing R410A with R32 can, in certain cases, impact lubrication efficiency. The viscosity of the oil within the compressor might be slightly higher than what R32 requires.

2. Amperage

The compressor’s electrical current consumption, or amperage, will be affected by the switch from R410A to R32. Ideally, maintaining the nominal electrical consumption of the compressor, representing the equipment’s characteristics when operating with R410A, is desirable.

Studies have shown that to achieve this nominal consumption value, the system should be charged with only 90% of the specified R410A weight. A charge greater than 90% could lead to an elevated electrical consumption above nominal levels, resulting in abnormal compressor heating and reduced equipment lifespan.

This is because the transition to R32 leads to an increase in the refrigerant’s mass flow rate, resulting in higher discharge pressure. This higher discharge pressure causes an increase in electrical current, and thus, power input.

3. Cooling Capacity

The cooling capacity provided by the compressor will also be impacted by the change from R410A to R32. For instance, considering a 90% load in grams compared to the R410A load, there will be a roughly 10% reduction in cooling capacity. In the graph example, cooling capacity drops from 2.4 kilowatts to 2.2 kilowatts.

Similarly, a 95% load compared to the R410A load leads to a ~5% increase in cooling capacity, but with higher-than-nominal electrical current consumption.

At a 100% load compared to the R410A load, the cooling capacity remains the same as the original equipment, but with higher-than-nominal electrical current consumption.

For a 105% load compared to the R410A load, there’s around a 5% decrease in cooling capacity, with higher-than-nominal electrical current consumption.

4. Discharge Temperature

With this transition, the refrigerant’s temperature at the compressor’s outlet will notably increase, potentially affecting the compressor’s lifespan.

5. Safety

For safety reasons, it’s not recommended to switch from R410A to R32 without manufacturer authorization, even though R32 is slightly flammable.

https://youtu.be/z3Pg_nJma-I

What happens when you mix R22 with some of its substitutes?

Here, we present 14 compelling reasons to steer clear of these unfamiliar blends and refrain from introducing any gas other than R22 into the system.

  • It can lead to a reduction in cooling capacity.
  • It might result in a loss of efficiency, leading to increased electricity consumption. Consequently, this can lead to a rise in the average compressor temperature, impacting the lubricant and the machine’s lifespan.
  • There’s a possibility that the discharge temperature of the mixture at the compressor’s outlet will be higher than normal.
  • Depending on the blend, issues with lubrication might arise.
  • For instance, the combination of gases like R22 and R417A can lead to unpredictable pressures and temperatures, thus negatively impacting efficiency and durability.
  • The unpredictability of pressures, temperatures, and the loss of oil return could potentially harm the system.
  • Excessive slippage might occur in the resulting blend. Remember, slippage refers to the increase in refrigerant temperature, as observed in the evaporator, for example.
  • A high slip value, such as in the evaporator, could result in very high temperatures at its outlet, thereby affecting the cooling process.
  • In cases where the mixture has a high slip value, the temperature at the evaporator’s outlet might become excessively high. This could consequently result in a compressor suction temperature above the normal range.
  • Even with slight variations in thermal loads, the new mixture could trigger freezing in the evaporator.
  • If the system employs pressure switches, abnormal pressures could activate these control devices.
  • Some substitutes aren’t compatible with the mineral oil traditionally used with R22, such as R407C, which impacts oil return.
  • If the equipment integrates a thermostatic expansion valve, its operation might be compromised as the superheat value measured by the bulb or a sensor becomes unpredictable.
  • The environmental impact should not be ignored. Blends affect the atmosphere and the environment. While not illegal, irresponsible usage contributes to environmental harm.

In essence, it’s crucial to avoid preparing refrigerant blends with R22. Each of these points demonstrates that responsible choices and adherence to safe practices are imperative for optimal performance and to safeguard both the equipment and the environment.

R22 VS R422

We will explore the differences between R22 gas and R422 refrigerant. Let’s get started!

What’s the Difference Between R22 and R422 Gases Used in Air Conditioning and Refrigeration?

https://youtu.be/F-JEWguBXvg
  • First of all, it’s important to highlight that R22 and R422 are two completely different gases. In fact, R422 has been specifically designed to replace R22 due to the issues caused by R22 to the ozone layer, whereas R422 does not present this problem.
  • R22 is a pure gas composed of a single component, while the refrigerants in the R422 family are formed by several components, such as refrigerant R125, refrigerant R134a, and isobutane gas R600.
  • Furthermore, while R22 has only one variant, there are several types of refrigerant gases in the R422 family, such as R422A, R422B, R422C, R422D, and R422E.
  • Although the gases in the R422 family have the same components, they vary in their proportions’ percentages.
  • It’s important to note that R22 can be charged either in liquid or gaseous phase, while the gases in the R422 family must be charged only in liquid phase.
  • Within the R422 family, the most recommended gas to replace R22 in air conditioning systems is R422D.
  • Additionally, in lower-temperature applications, the R422A refrigerant is widely used as a substitute for R22.
  • Both R22 and gases in the R422 family are non-flammable and non-toxic, classified as A1 in terms of safety and belong to group L1.
  • These refrigerants are compatible with a variety of lubricants, including mineral oil MO, alkylbenzene oil AB, and polyol ester oil POE.
  • However, gases in the R422 family generally have a high temperature glide, meaning their temperature changes during evaporation and condensation.
  • In terms of cooling capacity, the R422 family tends to be slightly lower than that of R22, usually with less than a 5% difference.
  • In some cases, using gases from the R422 family may require adjusting or regulating the expansion valve.
  • A notable difference between R22 and the R422 family is that the discharge temperature at the compressor outlet is lower in R422 gases. This extends the lifespan of the oil and compressor.
  • Refrigerants in the R422 family are also known by other names, such as Freon, MO 79, MO 49, MO 29, among others.
  • However, not everything is perfect with the R422 family, as they have a relatively high global warming potential (GWP) due to the presence of component R125.

Capillary for R410A

The Capillary for R410A is primarily utilized in air conditioning systems.

These are the 6 main Recommendations for selecting the dimensions of the capillary tube in an air conditioner that operates with R410A.

  1. The performance of capillary tubes in the air conditioner depends on both their length and diameter, as these factors determine their total restriction.
  2. It is essential to consider that a change in diameter, even by a percentage, can impact the flow more significantly than an equal change in tube length.
  3. Flow restriction can also be adjusted through tube length. When the tube is longer, the flow becomes slower. However, it is crucial to avoid excessively long lengths, as increasing restriction and excessively reducing flow can be uneconomical and inefficient.
  4. On the other hand, reducing the tube length gradually increases the flow until reaching a critical point, where each further reduction in length causes a faster increase in flow rate.
  5. It’s important to note that, at the point where the tube is very short, small changes in length can generate significant increases in flow. At this stage, the tube length no longer significantly affects the flow, and the tube acts more like an orifice than a capillary.
  6. For optimal operation and to avoid issues, it is recommended to maintain the tube length within a range of 5 to 16 feet (approximately 1.5 to 4.9 meters). While there are exceptions to this general rule, in most cases, staying within this range will be beneficial for the daily operation of the air conditioner.

In the following tables, we have the capillary measurements, with diameter in inches and length in meters, for the most common cooling capacities, in BTUs per hour.

D/L
in/m
0.047 in0.049
in
0.055
in
0.059
in
0.063
in
0.071
in
0.079
in
0.087
in
8000
BTU/H
0.3959 m0.5078 m1.006
m
1.505
m
2.169 m4.091 m
12000
BTU/H
0.2033 m0.2438
m
0.4583
m
0.6953
m
1.025
m
2.041
m
3.646
m
6.012
m
18000
BTU/H
0.2097 m0.2568 m0.3472 m0.6855 m1.295 m2.267 m
24000
BTU/H
0.2479 m0.3682 m0.6588 m1.17 m
Evaporator Temperature = 5°C Condenser Temperature = 50°C

36000 BTU/HDIAMETRO: 0.098 IN
LARGO: 0.9151

Alarm 10 Thermo King

Alarm 10 Thermo King can be described in the following table:

Alarm 10 Thermo King Color: Red ImmediateAction Required: Yes High compressor discharge pressure (or temperature)
If the unit shuts down, repair immediately. Otherwise, report the alarm at the end of the day. Alarm

Thermoking Fault Code 10:

This alarm is related to higher than normal discharge pressure.

  • If the fan is belt-driven, check its condition and tension.
  • Inspect the fan gearbox for jammed or worn bearings.
  • For electric condenser fan, verify voltage supply and motor behavior.
  • Check for a defective 12-volt battery.
  • A typical sign of a worn battery is if the unit loses power even before starting the engine.
  • Inspect for a faulty High-Pressure Cutout (HPCO) switch. HPCO switch is located on top of the compressor.
  • If the unit still doesn’t start, check HPCO switch voltage. Perform a voltage drop test to check for an open circuit. Trace the wiring circuit and verify fuses or switches connected to the circuit.

What to Do with Alarm 10 Thermoking?

In the following video prepared by CST Chilling Systems Training, some recommendations related to Alarm 10 Thermoking are presented:

  • Operate the unit in Cooling mode and check discharge and suction gauge readings.
  • If the system has a vapor injection for compressor cooling, operate the vapor injection valve to determine if it activates.
  • Check the resistance of the compressor discharge sensor.
  • The resistance in many Thermo King models should be approximately 86 kilohms at 25°C (77°F).
  • However, check your equipment’s sensor type.
  • Verify the discharge line temperature using a separate digital thermometer and compare it with the High-Pressure Temperature value displayed in the menu.
  • The unit will operate normally without the compressor sensor. However, the compressor’s high-temperature protection from the controller will not be active.

High-Pressure Cutout Switch (Alarm 17):

Thermo King High-Pressure Compressor Switches The High-Pressure Cutout Switch (2) is located on the compressor discharge service valve.

If the discharge pressure becomes too high, the switch opens the compressor contactor’s ground circuit.

The compressor stops immediately.

Evaporator and condenser fans continue to operate normally.

The controller detects that a high-pressure cutout switch or internal protector has been activated.

Verification of the condenser fan is performed.

Thermo king alarm code 63

Thermo king alarm code 63 is a red alert that demands immediate action when your diesel engine stops. Addressing this alarm promptly is crucial to ensure smooth operations.

There can be various reasons behind the code 63, making it a bothersome issue.

  • As a first step, check if the fuel filters are running low on fuel when this occurs and rule out any clogged pipelines. Most of the time, Thermo King Alarm 63 is triggered due to fuel-related problems.
  • When the engine halts, it is often referred to as an engine lock.
  • Heat can be a common cause of this issue.
  • Excessive heat in the exhaust system, engine, or ambient temperature can cause fuel to vaporize in the lines, leading to engine shutdown.
  • To address this problem effectively, allow the engine to cool down. Find a shady spot and park your vehicle. Let the engine rest for a few minutes.

What to do with Thermo King Alarm 63 Reefer?

  1. Download and inspect ServiceWatch data log information.
  2. Review the data using technical user level to determine the operating conditions when Alarm 63 was triggered.
  3. Use the running service test mode to replicate operating conditions as needed.
  4. Operating data can be viewed in technical mode.
  5. Perform a pre-trip test to identify the cause of the engine shutdown.
  6. Check for other alarm codes and proceed accordingly for each code.

What to do with Thermo King Alarm 63 Physically?

  1. Verify the fuel level and check the fuel pump for proper operation.
  2. Inspect the air filter and intake hose for any obstructions.

Understand the Thermo King Error 63:

Thermo King Fuel System:

  • The electric fuel pump (5) creates a vacuum in the supply line in the fuel tank (1).
  • Atmospheric pressure in the fuel tank (1) pushes the fuel upwards (line 6).
  • The fuel reaches the fuel filter (7) and part of it travels to the mechanical injection pump (9).
  • The fuel is distributed to the engine’s pistons through injectors (10) following the engine’s sequence.

Check the fuel level sensor.

  • Inspect the fuel level sensor, pins, and connector terminals.
  • Ensure there are no physical damages to the switch.
  • Check for damaged or corroded pins in the connector.
  • Check for voltage at the harness plug between the pins for negative and positive.
  • The voltage should be approximately 12 Volts DC.
  • Check the voltage at the harness plug between the pins.
  • Check the cable continuity from the harness pin to the microprocessor plug.
  • Place the ignition switch, run, and off in the OFF position before checking continuity.
  • It should be less than 10 ohms.

Thermo King Fuel Solenoid and Alarm 63:

  • When the fuel solenoid is energized, it allows fuel to flow to the injection pump, providing final fuel supply to the injectors.
  • This system works as a shutdown system to turn off the system.
  • Check if there is power to the fuel cutoff solenoid with the ignition on and the engine starting. If there is no power, make sure to test all fuses and relays. Also, inspect the wiring of the fuel cutoff solenoid for any damages.

Perform the necessary electrical checks to overcome code 63:

  1. Verify unit fuses.
  2. Check if the RPM sensor is functioning correctly.
  3. Review operating relay components and circuits and the fuel solenoid.
  4. Check for low battery voltage.
  5. Ensure all ground connections on the master ground plate are secure.
  6. Check for a seized compressor or motor.

Thermo King Fault Alarm 63:

The starter motor is responsible for providing the initial impulse to the diesel engine to allow it to reach its first revolutions.

The main components of the starter motor are:

  1. Pinion Gear
  2. Starter Motor
  3. Plunger
  4. Starter Solenoid
  5. Pinion Assembly
  6. Ring Gear

When the starter motor is energized, it engages the diesel engine through the coupling solenoid. Once the diesel engine starts spinning on its own, the solenoid separates the pinion and disconnects the starter motor.

R404A VS R407F

We will develop a comparison between two refrigerant gases: R404A and its substitute, R407F.

  • R407F is an excellent replacement for R404A in applications where the evaporator is above -10°C.
  • If R407F is used at lower temperatures, the compressor’s discharge temperature will be very high, affecting its operation and the viscosity of its lubricant.
  • Let’s start by explaining that both R404A and R407F are internally formed by a mixture of several gases, so both must always be charged in liquid phase.
  • For example, R404A contains approximately 4% R134A, 44% R125, and 52% R-143A.
  • Meanwhile, the refrigerant gas R407F is composed of the following gases: R-134A at 40%, R125 at 30.0%, and R-32 at 30%.
  • The glide of R404A is very low and lower than that of R407F. Remember that glide is the temperature change of the gas as it changes phase in the evaporator and condenser.
  • Both R404A and R407F do not deplete the ozone layer.
  • R407F has a global warming potential of 1825, while R404A has a GWP of 3920. Precisely, this high GWP value condemns the use of R404A due to ecological restrictions.
  • R407F is considered a refrigerant replacement for R404A in applications with high and medium temperatures in the evaporator.
  • Replacing R404A with R407F does not require any modifications in the system, as long as the evaporator temperature does not go below -10°C.
  • R407F is a perfect substitute, as it works similarly to R404A with POE type oil.
  • R407F is compatible with the components and joints of an existing R404A installation.
  • Both R404A and R407F are gases with a safety classification of A1 group L1, meaning they have low toxicity and are non-flammable.
  • R407F has excellent performance and cooling capacity, very similar to R404A.

Types of chilled water pumps

Chilled water pumps play a vital role in various applications, making them essential components in HVAC systems. Here’s an in-depth exploration of their functions and operations:

  1. Chilled Water Delivery: These pumps efficiently deliver chilled water to machines that require continuous cooling, ensuring optimal performance and reliability.
  2. Air Handling Units and Fan Coils: Chilled water pumps are employed to send chilled water to air handling units and fan coils, regulating indoor temperature with precision.
  3. Condenser Cooling: Pumps circulate water to cool the condenser in refrigeration circuits, maintaining optimal heat exchange.
  4. Special Cold Rooms and Industrial Processes: Chilled water pumps effectively cool special cold rooms and cater to cooling requirements in diverse industrial processes like ice rinks.
  5. Liquid Refrigerant Pumps: In refrigeration systems with flooded evaporators, these pumps, constructed from stainless steel, ensure seamless compatibility with the fluid.
  6. Well Pumps: Well pumps are used to replenish evaporated water in cooling towers, ensuring proper water levels for efficient cooling.
  7. Positive Displacement Pump for Oil: These pumps facilitate lubrication of components like compressors and feed hydraulic systems, ensuring smooth operation.

Centrifugal Pump Operation: Unveiling the Mechanism

Centrifugal pumps, pivotal in chiller systems, follow a sophisticated operational process:

  • The pump receives fluid in a liquid state through its center.
  • The impeller, or pump wheel, rotates due to the motor’s rotation, generating centrifugal forces.
  • Centrifugal force propels the liquid from the center of the wheel to its outer end.
  • The impeller’s curved shape allows the fluid to stay longer, resulting in higher speed.
  • The fluid gains kinetic energy, which must be converted into pressure.
  • Energy transformation occurs as the fluid passes through a nozzle, gradually reducing its speed while increasing the area of passage.
  • This conversion leads to the gradual transformation of kinetic energy into pressure.
  • The fluid exits the pump casing with high pressure, ready for its designated cooling tasks.

Essential Tips for Optimal Pump Performance

Understanding crucial pump care and maintenance is vital for HVAC system efficiency:

  • Never start the pump without sufficient water to prevent damage to seals and bearings.
  • Ensure proper priming to fill the suction pipe with water for seamless operation.
  • Prevent cavitation, which can damage the pump, by maintaining sufficient pressure in the suction and avoiding obstructions in the pipeline.
  • Always use motors with matching speeds and power to ensure smooth functioning.
  • Precise alignment of pump components, such as motors and shafts, is critical to prevent bearing damage.
  • Install necessary accessories, like valves and filters, to optimize pump operation.

Water Hammer and How to Avoid It

Water hammer, sudden pressure fluctuations when closing valves or turning the pump on and off abruptly, can lead to equipment damage. Soft starters with progressive start and stop mechanisms help avoid water hammer, preserving the system’s integrity.

Condensation Water Circuit and Primary Pump Circuit

Discover the functions of cooling towers, condenser water pumps, and water treatment systems in water-cooled condensers, efficiently dissipating heat from chillers.

The primary pump circuit plays a crucial role in circulating water through chillers to achieve optimal fluid conditioning. Its proper maintenance ensures optimal performance and flow through the chiller components.

Secondary Pump Circuit: Enhancing Distribution

The secondary pump circuit drives frozen water to different distribution systems like fan coils and air management units, overcoming frictional resistance in the network. The hydraulic decoupler acts as a balance line, ensuring stable pump operation and preventing operational issues.

Explore the various chilled water plant installations and their specific pumping schemes for increased efficiency and energy conservation.

Join us in this comprehensive guide to chilled water pumps, and empower yourself with knowledge for effective HVAC system management. Optimize pump performance and enhance your HVAC system’s overall efficiency today!

R448A VS R507A

We are going to develop a comparison between TWO refrigerant gases: the R507A and its substitute, the R448A.

  • Let’s start by saying that both the R507A and the R448A are internally composed of a mixture of several gases. Therefore, although the R507A has minimal glide, it is better for both gases to be charged in liquid phase.
  • The R-507A is an azeotropic blend, consisting of the gases R-125 and R-143a, each comprising 50%.
  • The R507A is known for its chemical stability, good thermodynamic properties, and low toxicity. Its main application is in low and medium-temperature installations.
  • On the other hand, the refrigerant gas R448A is composed of a mixture of gases: R32 at 26%, R1234ze at 7%, R134a at 21%, R125 at 26%, and R1234yf at 20%.
  • The glide of R507A is very low, and lower than that of R448A. Recall that glide is the temperature change of the gas while changing phase.
  • Neither R404A nor R448A harm the ozone layer.
  • The R448A has a global warming potential (GWP) of 1387, whereas R507A has a GWP of 3985. Precisely this high GWP value is what condemns the use of R507A due to ecological restrictions.
  • R448A is considered a replacement refrigerant for R507A in low and medium-temperature applications in the evaporator.
  • The transition from R507A to R448A does not require any modification in the compressor, as the discharge temperature with R448A is very similar to that of R507A.
  • R448A is a perfect substitute because it works just as well as R507A with POE type oil.
  • R448A is compatible with the components and seals of an existing R507A installation.
  • Both R507A and R448A are gases with a safety classification of A1, group L1, meaning they have low toxicity and are non-flammable.

R410A refrigerant poe 68 oil

We are going to talk about the type of oil used in an air conditioning unit with a capacity of 12000 BTU per hour, which operates with R410A refrigerant gas.

  • Firstly, we must mention that most 12000 BTU per hour air conditioning units use rotary compressors. These compressors are more cost-effective to manufacture, compact, and offer high performance, low noise levels, and acceptable durability.
  • Now, it’s time to answer the question: What type of oil does the rotary compressor in a 12000 BTU per hour air conditioning unit use?
  • Logically, the characteristics of the lubricant will depend on the compressor manufacturer. However, in many cases, we are not aware of the machine’s technical specifications, and as specialized technicians, we must perform an oil change in the compressor.
  • So, the question arises again: What oil should we use when we are not aware of the compressor’s technical specifications and need to perform maintenance by changing the old lubricant?
  • In such cases, we can generalize and say that the replacement oil should have similar technical characteristics to the original oil and belong to a reputable brand that guarantees the success of our work.
  • Considering the above, the lubricant that we propose as a perfect alternative for these situations is the POE 68 oil, which in most cases is an excellent option to replace the old oil.
  • The POE 68 oil has a viscosity close to 68 centistokes at 40°C, which ensures optimal performance at the working temperatures of the refrigerant in the equipment.
  • It is essential to remember that oil return can be challenging in split-type air conditioning systems because the oil must travel from the evaporator in the indoor unit inside the room back to the compressor in the outdoor unit outside the room.
  • During this process, problems may arise that affect the proper return of the lubricating oil, such as improper inclination or positioning of the return pipes. However, the type of lubricant is crucial for the correct functioning of the equipment.
  • When the oil does not return adequately to the compressor, there can be insufficient lubrication, leading to premature compressor wear and a decrease in its lifespan. Additionally, excess oil in the evaporator can affect the system’s performance and reduce its efficiency.
  • Not only is POE 68 oil a perfect alternative for rotary compressors due to its quality and viscosity, but it is also important for this oil to have a viscosity stability index close to or higher than 100.
  • Let’s remember that the viscosity stability index is a numerical measure that describes how the viscosity of a lubricating oil varies with changes in temperature.
  • When a lubricating oil has a viscosity index of 100, it is considered to have very stable viscosity over a wide range of temperatures. As the viscosity index decreases below 100, it indicates that the oil’s viscosity tends to change more significantly with temperature variations.
  • In this case, according to the table, this POE 68 oil has a viscosity index of 120.
  • So we can conclude that the POE 68 oil not only has the perfect viscosity but must also have the capacity to stabilize this viscosity value.

Exit mobile version